尺寸計算
風管尺寸=風量/風速
風量(liang)=房間面積*房間高*換(huan)氣次數
例子:風量(liang)4萬,風速9m/s,
得風管尺(chi)寸=40000/9/3600=1.23平方
1.23=1.5*0.82
所以 風管尺寸為1500*800 。
管道直徑設計計算步驟:
1、繪制(zhi)通(tong)風或(huo)空調(diao)系統軸測圖,對(dui)各管(guan)段進行編號,標注長度和風量。管(guan)段長度一(yi)般按(an)兩管(guan)件(jian)中(zhong)心(xin)線(xian)長度計算,不(bu)扣除管(guan)件(jian)(如(ru)三通(tong),彎(wan)頭)本身的長度。
2、確定合理的空氣(qi)速(su)流
風(feng)(feng)管內的(de)空(kong)氣流速對通風(feng)(feng)、空(kong)調系(xi)統(tong)的(de)經(jing)濟(ji)型有(you)較大(da)的(de)影響。流速高,風(feng)(feng)管斷(duan)(duan)面小,材料耗(hao)用(yong)(yong)(yong)(yong)少,建(jian)造費用(yong)(yong)(yong)(yong)小;但是系(xi)統(tong)的(de)阻(zu)力(li)大(da),動(dong)力(li)消(xiao)耗(hao)增大(da),運用(yong)(yong)(yong)(yong)費用(yong)(yong)(yong)(yong)增加(jia)(jia)。對除(chu)塵(chen)系(xi)統(tong)會(hui)(hui)增加(jia)(jia)設(she)備和(he)管道(dao)的(de)磨損,對空(kong)調系(xi)統(tong)會(hui)(hui)增加(jia)(jia)噪聲。流速低,阻(zu)力(li)小,動(dong)力(li)消(xiao)耗(hao)少;但是風(feng)(feng)管斷(duan)(duan)面大(da),材料和(he)建(jian)造費用(yong)(yong)(yong)(yong)大(da),風(feng)(feng)管占用(yong)(yong)(yong)(yong)的(de)空(kong)間也增大(da)。對除(chu)塵(chen)系(xi)統(tong)流速過低會(hui)(hui)使粉塵(chen)沉積堵塞管道(dao)。